current and voltage harmonic analysis of the oil production enterprise with abruptly variable load
Clicks: 5
ID: 165460
2019
Article Quality & Performance Metrics
Overall Quality
Not rated
Combines reader engagement with the AI quality analysis. This
article has not been analysed, so there is no overall score —
reader engagement is measured and shown alongside.
Reader Engagement
Steady Performance
1.2
/100
5 views
4 readers
AI Quality Assessment
Not analyzed
Readership in this journal
SteadyRanked #28 of 28 articles by views in asian economic and financial review
Most read
Least read
Bar heights use a square-root scale.
Mint this article as an NFT
Not yet mintedCreate a permanent, verifiable on-chain record of this article on the Scimatic Network. The NFT is held in your Journament account, and you can withdraw it to your own wallet at any time.
5
SUSD
one-off · no wallet required
Abstract
The monitoring results of 6 kV diesel power plant mode parameters are presented in the paper. The diesel power plant supplies the drilling unit of the oil production enterprise. The main goal of the paper is to estimate electric power quality indexes connected with voltage unsinusoidality of the monitored off-grid power system, to compare them with specified in State Standard 32144-2013 [1] and to provide high harmonics reduce methods. The real mode parameters measurements of 3600 kVA diesel power plant in different technological processes connected with oil production were used during the research. The MATLAB software and integrated Fourier transform function were applied to elaborate the mode parameters measurements. Based on harmonic analysis generalized results it is obtained that in many technological processes electric power quality indexes fail to meet the requirements of State Standard 32144-2013 [1]. The filter compensating device with reactive power 1350 kvar installed on 6 kV bus doesn’t allow to supply required electric power quality indexes. The DC drive thyristors rectifiers and the frequency converters of the asynchronous motors of the drill unit parts are the main sources of high harmonics in steady-state modes. The harmonic composition essential changes and electric power quality indexes are reduced due to load power dumps and surges. The high harmonics in such modes are caused by transients in synchronous generators providing supply of the considered power system. The quick-operating electric energy storage system with active power filter function [2] has been proposed as a method to reduce the harmonics.
| Reference Key |
vyacheslav2019e3scurrent
Use this key to autocite in the manuscript while using
SciMatic Manuscript Manager or Thesis Manager
|
|---|---|
| Authors | ;Zyryanov Vyacheslav;Khatylenko Roman;Potapenko Anton |
| Journal | asian economic and financial review |
| Year | 2019 |
| DOI |
10.1051/e3sconf/201911404002
|
| URL | |
| Keywords |
Citations
No citations found. To add a citation, contact the admin at info@scimatic.org
Comments
No comments yet. Be the first to comment on this article.