Transforming Data Centers in Active Thermal Energy Players in Nearby Neighborhoods

Clicks: 278
ID: 110081
2018
Article Quality & Performance Metrics
Overall Quality
Not rated
Combines reader engagement with the AI quality analysis. This article has not been analysed, so there is no overall score — reader engagement is measured and shown alongside.
AI Quality Assessment
Not analyzed
Readership in this journal
Steady

Ranked #91 of 275 articles by views in sustainability

Most read Least read

Bar heights use a square-root scale. Only the 120 most-read articles are drawn; the journal has 275 in total.

Mint this article as an NFT
Not yet minted

Create a permanent, verifiable on-chain record of this article on the Scimatic Network. The NFT is held in your Journament account, and you can withdraw it to your own wallet at any time.

5 SUSD one-off · no wallet required
Abstract
In this paper, we see the Data Centers (DCs) as producers of waste heat integrated with smart energy infrastructures, heat which can be re-used for nearby neighborhoods. We provide a model of the thermo-electric processes within DCs equipped with heat reuse technology, allowing them to adapt their thermal response profile to meet various levels of hot water demand. On top of the model, we have implemented computational fluid dynamics-based simulations to determine the cooling system operational parameters settings, which allow the heat to build up without endangering the servers’ safety operation as well as the distribution of the workload on the servers to avoid hot spots. This will allow for setting higher temperature set points for short periods of time and using pre-cooling and post-cooling as flexibility mechanisms for DC thermal profile adaptation. To reduce the computational time complexity, we have used neural networks, which are trained using the simulation results. Experiments have been conducted considering a small operational DC featuring a server room of 24 square meters and 60 servers organized in four racks. The results show the DCs’ potential to meet different levels of thermal energy demand by re-using their waste heat in nearby neighborhoods.
Reference Key
antal2018sustainabilitytransforming Use this key to autocite in the manuscript while using SciMatic Manuscript Manager or Thesis Manager
Authors Marcel Antal;Tudor Cioara;Ionut Anghel;Claudia Pop;Ioan Salomie;Antal, Marcel;Cioara, Tudor;Anghel, Ionut;Pop, Claudia;Salomie, Ioan;
Journal sustainability
Year 2018
DOI
10.3390/su10040939
URL
Keywords

Citations

No citations found. To add a citation, contact the admin at info@scimatic.org

No comments yet. Be the first to comment on this article.